Xtralis is the leading global provider of powerful solutions for the early detection and visual verifications of smoke, fire, gas and security threats. Our technologies prevent disasters by giving users time to respond before life, critical infrastructure or business continuity is compromised. We protect high-value and irreplaceable assets belonging to the world’s top governments and businesse

VESDA PRODUCTS

VLF-250 &  500_P.png

VLF

The VESDA VLF by Xtralis is an aspirating smoke detector ideal for small, business-critical spaces. Available in two models, the VLF-250 covers up to 250 m2 (2,690 sq. ft.), and the
VLF-500 covers areas up to 500 m2 (5,380 sq. ft.). 

Model Numbers: VLF-250, VLF-500

FEATURES  

  • Out-of-the-box installation and commissioning

  • Ultrasonic airflow sensing

  • Laser-based absolute smoke detection

  • Pre-engineered pipe network designs

  • Programmable alarm thresholds

  • Clean air barrier optics protections

  • Instant recognition display

  • Instant Fault Finder™

  • AutoLearn™ Smoke

  • AutoLearn™ Flow

  • Field service access door

  • Multiple event logging (in separate logs), up to 18,000 events

  • Offline/online configuration capability

APPLICATIONS  

The Xtralis VESDA VLF is a cost-effective solution for areas such as:

  • Local telecommunication exchanges

  • Air handling units

  • Smaller server rooms

  • Correctional facilities

  • Control rooms

  • Utility control hubs

  • Switch rooms

  • Railway signal hubs

  • Storage facilities

  • Cabinets

  • Hazardous areas (Class 1 Div 2)

  • Substations

CERTIFICATIONS 

  • UL, ULC, FM, CFE, LPCB, VdS,VNIIPO

  • AFNOR, ActivFire, CE - EMC and CPD

  • CSFM

  • FM Hazardous Locations: Suitable for Class 1, Division 2, Groups A, B, C and D

  • EN 54-20 (VLF-250)
    Class A (12 holes / 0.12% obs/m)
    Class B (12 holes / 0.35% obs/m)
    Class C (12 holes / 0.80% obs/m)

  • EN 54-20 (VLF-500)
    Class A (30 holes / 0.05% obs/m)Class B (30 holes / 0.15% obs/m)
    Class C (30 holes / 0.32% obs/m)

VLC

The VESDA VLC by Xtralis is an aspirating smoke detector that provides very early warning in single and small environments where space is at a premium. The VESDA VLC aspirating smoke detector is available in two versions, one that interfaces via relays only (RO) and one that interfaces via relays and VESDAnet (VN). The VESDA VLC-EX detector has been specifically designed to provide all the benefits of ASD for the protection of hazardous applications with Zone 2 classification.

Model Numbers: VLC-500, VLC-505, VLC-500-EX, VLC-505-EX, VLC-EX-US 

VLC_P.png

FEATURES  

  • Out-of-the-box installation and commissioning

  • Ultrasonic airflow sensing

  • Laser-based absolute smoke detection

  • Pre-engineered pipe network designs

  • Programmable alarm thresholds

  • Clean air barrier optics protections

  • Instant recognition display

  • Instant Fault Finder™

  • AutoLearn™ Smoke

  • AutoLearn™ Flow

  • Field service access door

  • Multiple event logging (in separate logs), up to 18,000 events

  • Offline/online configuration capability

APPLICATIONS  

The Xtralis VESDA VLF is a cost-effective solution for areas such as:

  • Local telecommunication exchanges

  • Air handling units

  • Smaller server rooms

  • Correctional facilities

  • Control rooms

  • Utility control hubs

  • Switch rooms

  • Railway signal hubs

  • Storage facilities

  • Cabinets

  • Hazardous areas (Class 1 Div 2)

  • Substations

CERTIFICATIONS 

  • UL, ULC, FM, CFE, LPCB, VdS,VNIIPO

  • AFNOR, ActivFire, CE - EMC and CPD

  • CSFM

  • FM Hazardous Locations: Suitable for Class 1, Division 2, Groups A, B, C and D

  • EN 54-20 (VLF-250)
    Class A (12 holes / 0.12% obs/m)
    Class B (12 holes / 0.35% obs/m)
    Class C (12 holes / 0.80% obs/m)

  • EN 54-20 (VLF-500)
    Class A (30 holes / 0.05% obs/m)Class B (30 holes / 0.15% obs/m)
    Class C (30 holes / 0.32% obs/m)

VLS & VLP_P.png

VLP

The VESDA VLP by Xtralis is the flagship of the VESDA aspirating smoke detector product line. Using unique detection principles, the VLP has an alarm sensitivity range of 0.005%–20% obscuration/m (0.0015%–6.25% obscuration/ft). The detector can form part of a modular system with the display, programmer and VESDAnet modules installed in a remote location or as a "self-contained" system by replacing the detector's panels with display and/or programmer modules. With the display and programmer remote, the user interfaces for many Xtralis VESDA VLP detectors can be grouped together in a cabinet for easy programming. 

FEATURES  

  • Wide sensitivity range

  • Laser based smoke detection

  • 4 configurable alarm levels

  • High efficiency aspirator

  • Four inlet pipes

  • Airflow supervisor per sampling pipe

  • Clean air barrier optics protection

  • Easy to replace air filter

  • 7 programmable relays

  • VESDAnet™

  • AutoLearn™

  • Referencing

  • Event log

  • Modular design

  • Recessed mounting option

The Xtralis VESDA VLP is ideal for protecting areas such as:

  • Aircraft hangars

  • Atria

  • Auditoriums

  • Cable tunnels/trays

  • Casinos

  • Clean rooms

  • Cold rooms

  • Computer rooms

  • Control rooms

  • Dormitories

  • EDP environments

  • Historical buildings

  • Hospitals

  • Hotels

  • Laboratories

CERTIFICATIONS 

  • UL, ULC, FM, CFE, LPCB, VdS,VNIIPO

  • AFNOR, ActivFire, CE - EMC and CPD

  • CSFM

  • EN 54-20
    Class A (30 holes / 0.05% obs/m)
    Class B (60 holes / 0.06% obs/m)
    Class C (100 holes / 0.08% obs/m)

VLS & VLP_P.png

VLS

The VESDA VLS by Xtralis is similar to the flagship VESDA VLP aspirating smoke detector but also includes a valve mechanism in the inlet manifold and software to control the airflow from the four sectors (pipes). This configuration enables a single VESDA zone to be divided into four separate sectors, for example, distinguishing between separate voids within a room. The VLS locates the origin of smoke by identifying the first sector (pipe) with the highest level of smoke and then continues to sample from all sectors to monitor fire growth. The VLS provides four alarm levels for each individual pipe (Alert, Action, Fire 1 and Fire 2). Sector factors (sensitivity) can be set individually to ensure the optimal alarm thresholds are applied for each sector. An extra LED indicates when the first alarm sector has been established. 

FEATURES  

  • ndividual pipe identification

  • Adaptive Scan Threshold

  • Wide sensitivity range (0.005 - 20% obscuration/m and 0.0015 - 6% obscuration/ft)

  • Laser-based smoke detection covering 2,000 m2 or 20,000 sq. ft

  • VESDAnet™ communication

  • 4 alarm levels per sector

  • High efficiency aspirator

  • Clean air barrier optics protection

  • Easy to replace air filter

  • 7 or 12 programmable relays option

  • AutoLearn™

  • Event log

  • Recessed mounting

APPLICATIONS  

The Xtralis VESDA VLS is ideal for protecting several rooms or separate areas within a building, such as those within:

  • Casinos - small gaming rooms

  • Clean rooms - small, adjacent clean rooms

  • Computer rooms - equipment cabinets

  • Control rooms - equipment cabinets

  • Dormitories/prisons - up to 4 rooms or cells

  • Historical buildings - separate rooms

  • Hospitals - separate operating theaters or laboratories

  • Hotels - guest rooms

  • Laboratories - separate fume hoods or rooms

  • Libraries/archival storage - storage rooms

  • Museums/art galleries - small display rooms

CERTIFICATIONS 

  • UL, ULC, FM, CFE, LPCB, VdS,VNIIPO

  • AFNOR, ActivFire, CE - EMC and CPD

  • CSFM

  • EN 54-20
    Class A (40 holes / 0.08% obs/m)
    Class B (40 holes / 0.23% obs/m)
    Class C (60 holes / 0.65% obs/m)

VLI

The VESDA VLI by Xtralis is an industry first early warning aspirating smoke detection (ASD) system, designed to protect industrial applications and harsh environments of up to 2000 m2 (21,520 sq. ft.). The VLI detector combines a fail-safe Intelligent Filter (patent pending) with an advanced clean-air barrier for optics protection allowing the use of absolute detection and a long detection chamber life without the need for re-calibration. 

FEATURES  

  • Suitable for Class 1 Division 2 applications
    - Groups A,B,C & D

  • Up to 2000 m2 (21,520 sq. ft.) coverage

  • Up to 4 inlet pipes

  • Total pipe length up to 360 m (1181 ft)

  • Five (5) high intensity status LEDs for greater visibility

  • Robust absolute smoke detection

  • Intelligent Filter (patent pending)

  • Lint Trap to capture fibrous particulates

  • Sub-sampling Probe (inertial separator)

  • Secondary Filter

  • Clean air barrier for optics protection

  • Referencing

  • AutoLearn™ Smoke and Flow

  • Clean Air Zero™

  • Air-path monitoring

  • Five (5) relays (Fire, Fault and 3 configurable)

  • Relays configurable as latching or non-latching

  • Expandable GPI and relays

  • Ultrasonic flow sensing

  • Xtralis VSC, Xtralis VSM4 and ASPIRE software support

  • IP66 Enclosure

  • Easy mounting with steel support bracket

  • Modular field replaceable parts for ease of servicing

  • Local USB configuration port

  • Easy cable termination access

  • Imperial and metric pipe ports

  • Rubberized finish to external housing

APPLICATIONS  

The VESDA VLI is the ideal solution for such areas as:

  • Mines

  • Manufacturing and processing plants

  • Conveyors

  • Petrochemical plants

  • Tunnels

  • Grain silos

  • Power generation facilities

  • Timber, pulp and paper plants

  • Warehouses

  • Water treatment plants

  • Transportation hubs

  • Fertilizer plants

  • Abattoirs

  • Laundries

  • Cold stores

  • Equipment and machinery

  • Textile plants

  • Elevator shafts

  • Equestrian centers

  • Livestock/animal facilities

CERTIFICATIONS 

  • UL

  • ULC

  • FM

  • ActivFire

  • CE

  • LPCB

  • NF

  • SIL 2 as per IEC 61508

  • EN 54-20
    - Class A (24 holes / Alert = 0.06% obs/m)
    - Class B (28 holes / Fire-1 = 0.15% obs/m)
    - Class C (60 holes / Fire-1 = 0.15% obs/m)

VLI_P.png

VEP

The VESDA-E VEP series of smoke detectors bring the latest and most advanced detection technology to provide very early warning and the best nuisance alarm rejection to a wide range of applications. Built on the Flair detection technology and years of application experience, VEP detectors achieve consistent performance over their lifetime via absolute calibration. In addition, the VEP delivers a range of revolutionary features that provide user value. 

Model Numbers: VEP-A00-1P, VEP-A00-P, VEP-A10-P

FEATURES  

  • One and four pipe models for different applications

  • Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms

  • Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance

  • Four alarm levels and a wide sensitivity range deliver optimum protection for the widest range of applications

  • Intuitive LCD icon display provides instant status information for immediate response

  • Flow fault thresholds per port accommodate varying airflow conditions

  • Smart on-board filter retains dust count and remaining filter life for predictable maintenance

  • Extensive event log (20,000 events) for event analysis and system diagnostics

  • AutoLearn™ smoke and flow for reliable and rapid commissioning

  • Referencing to accommodate external environmental conditions to minimise nuisance alarms

  • Fully backward compatible with VLP and VESDAnet

  • Remote monitoring with iVESDA for system review and proactive maintenance

  • Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance

  • Industry first. Aspirating detector secondary monitoring and maintenance via WiFi

  • USB for PC configuration, and firmware upgrade using a memory stick

  • Two programmable GPIs (1 monitored) for flexible remote control

  • Field replaceable sub-assemblies enable faster service and maximum uptime

APPLICATIONS  

  • Accommodation (Apartments, Hotels, Shops and Offices)

  • Correctional Facilities

  • Clean Rooms

  • Cold Storage

  • Cultural/Heritage

  • Data & Telecom

  • Education

  • Hospitals & Healthcare

  • Insurance

  • Marine

  • Nuclear Facilities

  • Offices

  • Oil & Gas

  • Portable Switch Rooms

  • Power Generation

  • Records Storage

  • Retail

  • Transportation

  • Wind Power Generation

  • Warehousing

  • And more...

CERTIFICATIONS 

  • UL

  • ULC

  • FM

  • ActivFire

  • CE

  • VdS

  • CPR

  • EN 54-20, ISO 7240-20, Four Pipe VEP

  • - Class A (40 holes / Fire 1 = 0.028% obs/m)
    -  Class B (80 holes / Fire 1 = 0.027% obs/m)
    -  Class C (100 holes / Fire 1 = 0.056% obs/m)

VEP_P.png

VEU

The VEU series of aspirating smoke detectors are the premium detector of the VESDA-E range. An Ultra-wide sensitivity range; 15 times greater than VESDA VLP, and provision for more sampling holes provide an increased coverage in high airflow applications by at least 40%. Considerably longer linear pipe runs and extended branched pipe network configurations cater perfectly to applications with higher ceilings providing an increased coverage by up to 80% whilst allowing convenient detector mounting for ease of service and maintenance. A range of revolutionary new features provide unsurpassed detection performance, flexibility, field programmability, connectivity and reduced total cost of ownership. 
Model Numbers: VEU-A00, VEU-A10

FEATURES  

  • Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms

  • Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance

  • Four alarm levels and an ultra wide sensitivity range deliver optimum protection for the widest range of applications

  • Intuitive LCD icon display provides instant status information for immediate response

  • Flow fault thresholds per port accommodate varying airflow conditions

  • Smart on-board filter retains dust count and remaining filter life for predictable maintenance

  • Extensive event log (20,000 events) for event analysis and system diagnostics

  • AutoLearn™ smoke and flow for reliable and rapid commissioning

  • Referencing to accommodate external environmental conditions to minimise nuisance alarms

  • Fully backward compatible with VLP and VESDAnet

  • Remote monitoring with iVESDA for system review and proactive maintenance

  • Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance

  • Industry first. Aspirating detector secondary monitoring and maintenance via WiFi

  • USB for PC configuration, and firmware upgrade using a memory stick

  • Two programmable GPIs (1 monitored) for flexible remote control

  • Field replaceable sub-assemblies enable faster service and maximum uptime

APPLICATIONS  

  • Accommodation (Apartments, Hotels, Shops and Offices)

  • Correctional Facilities

  • Clean Rooms

  • Cold Storage

  • Cultural/Heritage

  • Data & Telecom

  • Education

  • Hospitals & Healthcare

  • Insurance

  • Marine

  • Nuclear Facilities

  • Offices

  • Oil & Gas

  • Portable Switch Rooms

  • Power Generation

  • Records Storage

  • Retail

  • Transportation

  • Wind Power Generation

  • Warehousing

  • And more...

CERTIFICATIONS 

  • UL

  • ULC

  • FM

  • VdS

  • CE

  • CPR

  • ActivFire

  • EN 54-20, ISO 7240-20

  • -  Class A (80 holes / Fire 1 = 0.015% obs/m )
    -  C lass B (80 holes / Fire 1 = 0.026% obs/m)
    -   Class C (100 holes / Fire 1 = 0.062% obs/m)

VEA

VEA combines VESDA reliability & early warning smoke detection with pinpoint addressability. VEA uses patented multi-channel microbore tubes & patented air-sampling points with three sensitivity settings. VEA divides a protected space into sampling locations, to pinpoint threats for faster response. Features include field programmability, enhanced connectivity, and centralized test & maintenance to provide reduced total cost of ownership. VEA has a IP40-rated enclosure & is equipped with a powerful pump, providing up to 100 m (328 ft) microbore tube lengths. Using VSC for commissioning, a normalization process establishes flow performance parameters. Local smoke test ports are used during servicing to verify that the system is fully operational. Field replaceable components such as filter, smoke smoke sensor module, and pump & rotary valve result in less down time and ease of maintenance. 
Model Numbers: VEA-040-A00, VEA-040-A10

FEATURES  

  • Pinpoint addressability 

  • 40 addressable microbore tubes with individual sampling points

  • Assured detection with end to end system integrity monitoring

  • Interruption-free business operation with centralised testing and maintenance

  • Single sampling point or single tube blockage detection at set intervals 

  • Automatic sampling point presence and tube breakage detection at set intervals

  • Automatic sampling point cleaning at set intervals

  • Three sensitivity settings for the sampling points

  • Variable length capillary tubes, up to 100 m (328 ft)

  • Laser-based absolute smoke detection

  • Coarse particle filtering and clean air barrier for optics protection

  • Reliable linear pump technology

  • LEDs for alarm and fault signalling

  • 3.5” colour touch screen for status review

  • Seven programmable relays

  • Two GPIs, monitored and unmonitored

  • Xtralis VSC and VSM4 PC software support

  • iVESDA application for system monitoring on mobile devices

  • IP 40 enclosure (not UL tested)

  • Easy mounting with steel support bracket

  • Field replaceable filter, smoke sensor module, pump and rotary valve

  • VESDAnet networking

  • Ethernet 100BASE-T

  • WiFi, 802.11 b/g/n

  • Local host-mode USB port

  • Easy cable termination access

  • Event Log (20,000 events)

APPLICATIONS  

As a multi-channel addressable system, the VEA detector is able to divide a protected space into sampling locations, enabling the localization of potential sources of fire for faster incident
response. The detectors are suitable for protection of areas where pinpoint location of fire events is essential, thus providing ideal fire detection solutions:

  • Offices

  • Hospitals

  • Schools

  • Prisons

  • Multi-story dwellings

  • Data Centers

  • Warehouses

CERTIFICATIONS 

  • UL

  • ULC

  • CSFM

  • ActiveFire

  • EN 54-20, ISO 7240-20: Class A, B and C

  • VdS

  • CE

VEU_P.png
VEA_P.png

VFT

The VESDA VFT-15 by Xtralis is a unique and versatile high-sensitivity aspirating smoke detector able to pinpoint the source of incipient smoke to speed response, enhance investigation and minimize business disruption and downtime where location is critical and a visual search is impossible to perform quickly. VESDA VFT is the only aspirating smoke detector on today’s market to provide identification of up to 15 protected areas. 
Model Numbers: VFT-15, VFT-15-C

FEATURES  

  • O

  • VFT-15: 0.01% to 20% obscuration/m (0.003% to 6.10% obscuration/ft)

  • VFT:15-C: 1% to 20% obscuration/m (0.3% to 6.10% obscuration/ft)

  • 4 Alarms - Alert, Action, Fire 1, Fire 2

  • 15 x 50 m (15 x 164 ft) microbore sampling tubes

  • Enhanced 0.7 bar rotary vane vacuum pump

  • Ethernet TCP/IP

  • RS232 and RS485 Modbus

  • 5 relay outputs

  • Optional relay module

  • Coverage area of up to 1,500 m2 (16,150 sq ft) 

APPLICATIONS  

The Xtralis VESDA VFT is ideal for protecting several rooms or separate areas within a building, such as those within:

  • Clean rooms - small, adjacent clean rooms

  • Computer rooms - equipment cabinets

  • Control rooms - equipment cabinets

  • Elevators - hoistways, control rooms and lobbies

  • Historical buildings - separate rooms and object protection

  • Hospitals - separate operating theatres or laboratories

  • Hotels - guest rooms

CERTIFICATIONS 

  • VdS

  • EC/CPD EN54-20

  • FM

  • CSFM

VFT_P.png
bottom of page